CS175-275-575-875 Installation Guide 75
Events 49 and 50 require RX8w8, RX16w8, RX8i4 or RX16i4 wireless receivers to
operate.
If set to the follow condition, these events are 1 second.
"
1
When Event 48 is programmed, it is possible to program a user code's authorization to
select which output(s) a particular code activates.
See
Assigning authority level
on
page 43 for more information.
"
2
Always program Event 39, Fire alarm reset, to follow the event.
Location 60 Auxiliary output #2, event and time (two segments, ND)
Segment 1
Use the table in location 59 to select the event that activates auxiliary
output 2..
Segment 2
Program the timing from 0 to 255 (minutes or seconds, depending on
data programmed in segment 2, location 58). Program ‘0’ to make the
output follow the event.
Location 61 Auxiliary output #3, event and time (two segments, ND)
Segment 1
Use the table in location 59 to select the event that activates auxiliary
output 3.
Segment 2
Program the timing from 0 to 255 (minutes or seconds, depending on
data programmed in segment 3, location 58). Program ‘0’ to make the
output follow the event.
Location 62 Auxiliary output #4, event and time (two segments, ND)
Segment 1
Use the table in location 59 to select the event that activates auxiliary
output 4.
Segment 2
Program the timing from 0 to 255 (minutes or seconds, depending on
data programmed in segment 4, location 58). Program ‘0’ to make the
output follow the event.
Location 63 Autotest timing (three segments, ND)
Segment 1
Program the autotest interval from 1 to 255 hours/days.
Segment 2
Program the autotest report hour in 24-hour format. If the interval is in
hours, this segment is ignored.
Segment 3
Program the autotest report time. This is the number of minutes after
the hour.
Segment 4
Reserved
Location 64 Autotest control (one segment, FSD)
Segment 1
Program ‘1’ if the interval is in hours; Program ‘0’ if it is in days. Add
‘2’ to suppress the daily test or ‘3’ to suppress the hourly test if any
report has been sent.