Aritech ATS3000 Guía de usuario Pagina 39

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 71
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 38
ATS2000/3000/4000/4500 Manager’s Guide
37
12. TEST ZONE
Use this function to test if an individual zone is operating correctly.
To test a zone
1. Access menu option 12.
The display shows:
2. Enter the zone number you want to test and press [ENTER], or
press [ENTER] to exit and return to the menu.
3. If you selected a zone, one of four responses is displayed:
The zone is normal
e.g.
The zone is active
e.g.
There is a faulty condition due to cable tamper. The cabling to the zone
shows an OPEN circuit.
e.g.
There is a faulty condition due to cable tamper. The cabling to the zone
shows a SHORT circuit.
e.g.
4. Press [ENTER] to exit and return to the menu option display.
1. If a zone is active, open or short, the keypad emits a continuous tone. When
the status of the zone is changed to normal, the display is updated and the
tone stops.
2. If the zone is inhibited when a test is requested on it, the system uninhibits the
zone, conducts the test, and then returns the zone back to inhibited.
3. The test must be carried out within a pre-determined time. If the test is not
completed within this time, the option is exited.
Test Individual Zone:
Zone No:
NORMAL STATE on 12, Roller Doo
r
OPEN on 12, Roller Doo
r
SHORT on 12, Roller Door
A
CTIVE on 12, Roller Doo
r